...Installation and Operating Instructions for USAInstallation et fonctionnement pour CanadaSafety notice: If this s
CLEARANCES TO COMBUSTIBLESFloor ProtectionFloor protection under the F 3 CB woodstove, mustbe one of the following:1. Any non combustible material wi
CBDA11STOVE CLEARANCES UNPROTECTED SURFACES PROTECTED SURFACESTOP VENT/VERTICAL per NFPA 211 or CAN/CSA-B365-MSIDE REAR CORNER SIDE REA
&WALL SHIELD •Must be 30” wide and centered behind the stove•Must be 1” off the wall and 1” off the floor. •With standard legs, the shield mus
NOTICEAccessories for woodstoves for clearance reduction havebeen developed by many manufacturers. If not followingthe methods of the installati
WARNING:DO NOT INSTALL IN A BEDROOM/SLEEPINGROOM. THE STRUCTURAL INTEGRITY OF THEMOBILE HOMES FLOOR, WALL, CEILING/ROOFMUST BE MAINTAINED.OPERATIONB
Starting and Maintaining a FireBurn only solid wood directly on the bottomgrate of the stove, do not elevate the fire in anyway.The ash pan door on th
MAINTENANCEAsh remomal: OF COURSE, FOR YOURPROTECTION ALWAYS WEAR SAFETYGLOVES WHEN HANDLING THE ASH PAN.Ash removal will be required periodic
17FIGURE 17door gasketglassglass clips4. Remove all remaining debris from the glass area using a wire brush.5. Apply a small bead of gasket/stov
ACCESSORIESMany accessories have been manufactured for usewith the Jøtul F 3 CB. ONLY USE ACCESSORIESTHAT ARE SPECIFICALLY DESIGNED FORTHE JØTUL F 3
EXPLODED VIEW OF THE F 3 CB197376706564453542292624223146515552575922156222B6811127
TABLE OF CONTENTS:Standards and Safety Notices...3Installations...4Chimney Requirem
ALTERNATE FLOOR PROTECTIONAll floor protection materials must be non-combustible ie. metal,brick, stone, mineral fiber boards). Any combustible
Stoves and fireplaces must be installed to conform to local and national building regulations. Before preparing for the installation ofthe appl
STANDARDSThe F 3 CB wood stove has been tested and listedto;U.S. Standards: ANSI/UL 737 and ANSI/UL 1482.Canadian Standards: CAN/ULC-S627-M93Tests pe
INSTALLATIONIF THIS SOLID FUEL ROOM HEATER IS NOT PROPERLYINSTALLED A HOUSE FIRE MAY RESULT. FOR YOURSAFETY, FOLLOW THE INSTALLATION DIRECTIONS.CONTA
STOVE PIPECHIMNEY CONNECTORThe chimney connector is a single walled pipe usedto connect the stove to the chimney. For use with theF 3 CB the chimney
Prefabricated ChimneysIf a prefabricated metal chimney is to be used itmust be a chimney type that is tested and listed foruse with solid fuel burning
WALL PASS-THROUGHSWhen your installation unavoidably requires thechimney connector to pass through a combustible wallto reach the chimney, always cons
In CanadaThe Canada the standard has been established by theCanadian Standard Association. The installation mustconform to CAN/CSA-B365, Installation
Hearth-mount into a Masonry FireplaceThe F 3 CB may be installed into a masonry fireplaceprovided the opening is a minimum of 28 1/2 high.The short